Has anybody tried getting longer run times from UPS's by plugging
one UPS into another? Power goess off, the first UPS goes on batteries, and runs everything. When it quits, the second UPS senses it and goes on batteries, and runs the computer. And so indefinitely if you add more UPSs to get more runtime. It seems it me it would work except possibly : (1)The UPSs might not like the non-sinewave output of the first UPS, and (2)I don't know what kind of current they draw if they decide to recharge their batteries from an outer UPS. (This would suggest it's wise to unplug the outer UPS when the power goes off so nobody tries to recharge.) -- Ron Hardin On the internet, nobody knows you're a jerk. |
#2
![]() |
|||
|
|||
![]()
On Sat, 10 Mar 2007 10:14:47 GMT, Ron Hardin
wrote: Has anybody tried getting longer run times from UPS's by plugging one UPS into another? Power goess off, the first UPS goes on batteries, and runs everything. When it quits, the second UPS senses it and goes on batteries, and runs the computer. And so indefinitely if you add more UPSs to get more runtime. It seems it me it would work except possibly : (1)The UPSs might not like the non-sinewave output of the first UPS, and (2)I don't know what kind of current they draw if they decide to recharge their batteries from an outer UPS. (This would suggest it's wise to unplug the outer UPS when the power goes off so nobody tries to recharge.) Why not just take the battery out of the 2nd one and put it in parallel with the battery in the first one? It would be more efficient. |
#3
![]() |
|||
|
|||
![]() "Brenda Ann" wrote in message ... "Ron Hardin" wrote in message ... Has anybody tried getting longer run times from UPS's by plugging one UPS into another? Power goess off, the first UPS goes on batteries, and runs everything. When it quits, the second UPS senses it and goes on batteries, and runs the computer. And so indefinitely if you add more UPSs to get more runtime. It seems it me it would work except possibly : (1)The UPSs might not like the non-sinewave output of the first UPS, and (2)I don't know what kind of current they draw if they decide to recharge their batteries from an outer UPS. (This would suggest it's wise to unplug the outer UPS when the power goes off so nobody tries to recharge.) -- You're not going to extend your runtime near as much as you might think. If you had an UPS with a clean enough pseudo-sine waveform to even get the next one in line to power up stably (and you have to get into some very very good ones to do that, they basically have to be generator rated), then you have to deal with the issue of the other UPS'es in the chain not being 100% efficient, so you lose a lot of what you would have gotten from that first unit in the line. This of course follows up the chain. Just buy a bigger UPS!!! I use to sell them Burr |
#4
![]() |
|||
|
|||
![]()
Brenda Ann wrote:
You're not going to extend your runtime near as much as you might think. If you had an UPS with a clean enough pseudo-sine waveform to even get the next one in line to power up stably (and you have to get into some very very good ones to do that, they basically have to be generator rated), then you have to deal with the issue of the other UPS'es in the chain not being 100% efficient, so you lose a lot of what you would have gotten from that first unit in the line. This of course follows up the chain. Doesn't the UPS just pass along the input to the output as long as it's ok power? So I don't see the loss. The second UPS just passes along the output of the first UPS. -- Ron Hardin On the internet, nobody knows you're a jerk. |
#5
![]() |
|||
|
|||
![]()
On Sat, 10 Mar 2007 16:50:58 GMT, Ron Hardin
wrote: Brenda Ann wrote: You're not going to extend your runtime near as much as you might think. If you had an UPS with a clean enough pseudo-sine waveform to even get the next one in line to power up stably (and you have to get into some very very good ones to do that, they basically have to be generator rated), then you have to deal with the issue of the other UPS'es in the chain not being 100% efficient, so you lose a lot of what you would have gotten from that first unit in the line. This of course follows up the chain. Doesn't the UPS just pass along the input to the output as long as it's ok power? So I don't see the loss. The second UPS just passes along the output of the first UPS. That's more of a battery backup than a real UPS. |
#6
![]() |
|||
|
|||
![]()
If you want EXTENDED time, wait til the batteries die, remove them and run
wires to a car battery (can even be outside in a battery box ) DO NOT allow the internal charger in the UPS to charge the car battery, put a diode in line to block current going to the car battery but allowing the battery voltage to 'flow' to the UPS. A small trickle charger or floating battery charger can keep the car battery at full charge. You can use an old heavy extension cord ( like those orange ones you get to use outside ) to connect the battery and USP. Useful backup time should be anywhere from 6 to 24 hours depending on the draw ( how much your trying to power) and the quality ( number of plates ) of the battery. BE SURE the UPS uses batteries totaling 12 volts, before you even attempt this. Any damage you cause on your own equipment is your own fault ...... so if you don't know what your doing don't even try. and if you do ..... don't blame me ![]() "Ron Hardin" wrote in message ... Has anybody tried getting longer run times from UPS's by plugging one UPS into another? Power goess off, the first UPS goes on batteries, and runs everything. When it quits, the second UPS senses it and goes on batteries, and runs the computer. And so indefinitely if you add more UPSs to get more runtime. It seems it me it would work except possibly : (1)The UPSs might not like the non-sinewave output of the first UPS, and (2)I don't know what kind of current they draw if they decide to recharge their batteries from an outer UPS. (This would suggest it's wise to unplug the outer UPS when the power goes off so nobody tries to recharge.) -- Ron Hardin On the internet, nobody knows you're a jerk. |
#7
![]() |
|||
|
|||
![]()
In article ,
Ron Hardin wrote: Brenda Ann wrote: You're not going to extend your runtime near as much as you might think. If you had an UPS with a clean enough pseudo-sine waveform to even get the next one in line to power up stably (and you have to get into some very very good ones to do that, they basically have to be generator rated), then you have to deal with the issue of the other UPS'es in the chain not being 100% efficient, so you lose a lot of what you would have gotten from that first unit in the line. This of course follows up the chain. Doesn't the UPS just pass along the input to the output as long as it's ok power? So I don't see the loss. The second UPS just passes along the output of the first UPS. I have not done this but your expectation sounds reasonable. Many UPS units produce a trapezoid shape output but again I do not see a problem plugging one UPS into another. -- Telamon Ventura, California |
#8
![]() |
|||
|
|||
![]() "Ron Hardin" wrote in message ... Brenda Ann wrote: You're not going to extend your runtime near as much as you might think. If you had an UPS with a clean enough pseudo-sine waveform to even get the next one in line to power up stably (and you have to get into some very very good ones to do that, they basically have to be generator rated), then you have to deal with the issue of the other UPS'es in the chain not being 100% efficient, so you lose a lot of what you would have gotten from that first unit in the line. This of course follows up the chain. Doesn't the UPS just pass along the input to the output as long as it's ok power? So I don't see the loss. The second UPS just passes along the output of the first UPS. -- Ron Hardin On the internet, nobody knows you're a jerk. Ron, No! There power is checked to be sure it is 60cyc, close to 120 and steadies and it is filtered. Read the papers that came with it. Remember, you get what you pay for. I like "Minuteman". For your radio the way I do it is run them off a 12v car battery with a charger hooded to them. I can "take" the charger off if I hear Norse or just when I am DXing. If the power goes off they will still run for hours if you have a good battery and you can shut down the radios you don't have to have. ALWAYS HAVE A GOOD GROUND ROD GROUND for the radios and antennas! Burr |
#9
![]() |
|||
|
|||
![]()
David wrote:
Why not just take the battery out of the 2nd one and put it in parallel with the battery in the first one? It would be more efficient. It would be, but there's a catch. When the time comes to recharge the now much bigger battery, the original charging circuit probably couldn't handle the extra current. The greater the plate area, the more it starts looking like a short circuit as far as the circuitry goes. Most things being now built are made down to a cost instead of up to a quality standard. mike |
#10
![]() |
|||
|
|||
![]()
On Sun, 11 Mar 2007 01:27:50 GMT, m II wrote:
David wrote: Why not just take the battery out of the 2nd one and put it in parallel with the battery in the first one? It would be more efficient. It would be, but there's a catch. When the time comes to recharge the now much bigger battery, the original charging circuit probably couldn't handle the extra current. The greater the plate area, the more it starts looking like a short circuit as far as the circuitry goes. Most things being now built are made down to a cost instead of up to a quality standard. mike I've done this succesfully. I'm guessing the current is clamped, but the Triplett kept 3 big-ass batteries charged in a microwave shack. |
Reply |
|